Tried to prepare units 813 and 1163 for installation at 30 meters, but could not get them to boot and run with required length of cable. Red LED at circuit board
would stay on, or blink on and off. It is supposed to go off once the unit is running. Measured 8 V at the end of 30 meter cable with unit attached. Need to reduce this loss.

...

DC power supply in power enclosure is rated at 3 A, which will not
be large enough to drive system with 5 Licor 7500s, since each Licor needs about 0.9 A.

The beacon was running off a battery with an inverter. Connected
the beacon directly to AC and added the battery to the 2 that power
the data system and tower sensors.

...