FRONT: Requirements for Remote System Monitoring and Control

We need the ability to remotely monitor and control both S-Pol and CHILL, since we will want to remotely operate both radars.  Since S-Pol is likely to be located at least 1 hour away from Foothills Lab, we need the ability to fix problems without  minimum 2 hour round trip.

This document captures the requirements for remote monitoring and control.

Remote control of computers

We need the ability to cycle power on key servers in each radar.  For S-Pol, this would include:

Name

Function

circuits

gate

Gateway, web server

2

mgen

moment generation

2

pgen

product generation and raid

4

raid1

data storage

3

raid2

data storage

2

rpv8

digitizer

2

dxmit

digital transmitter

1

 In addition to power cycling to restart a stuck computer, we need the ability to turn off computers because

  1. the ambient air temperature is too high, or
  2. Commercial and generator power have failed, and the UPS batteries are low.

Other Power Control and Monitoring

  1. Transmitter
  2. Remote monitoring/control of UPS (via USB).  Eventually, we should be able to monitor the load (and battery condition, if available) of the 3 UPSs in the transmitter van.
  3. Generator and transfer switch control and monitoring.

Console Access

In addition to controlling power, we also need the ability to have remote console access to the remote computers, in case we need to debug booting issues (and can not remote login).

Environmental Monitoring

We need the ability to monitor key temperatures, voltages, and currents throughout each radar.  We need an auto-dialer that can notify a list of people of the following conditions:

(Please fill in this table).

Location

Item

Range

Transmitter

Klystron Temperature

20-80C

Transmitter Shelter

Ambient Temperature

 

Antenna

Antenna stops moving

 

Transmitter

Faults

 

Site

Power Failure

 

Site

Fire/smoke detection

 

If the new site has a landline, we can probably use our existing auto-dialer.  If we don't have a land-line, there are new dialers that use cell phones.  The autodialer needs to dial a list of numbers, which should be easily modified.  The autodialer does not have to give precise status for all conditions - it would be ok to require someone to access a web site at S-Pol to get more details.

Dialers

http://www.racoman.com/

http://www.autodialer-alarm.com/

Possible solutions:

Web Monitoring