6/4/08 Adams up and running for checkout.
One of the power supplies running 3 adams died. It suffered from thermal shutdown and dropped its output to 4vdc killing the adams. It's rating is 12Ain and was operating in the wind tunnel: not encouraging given prospects in central valley. After letting it cool, we restarted and measured the following currents and measured the profile adam running on a second supply:
Adam  | 
Amps  | 
 A-total   | 
 VDC   | 
 Comments   | 
|---|---|---|---|---|
downwind1  | 
2.3  | 
 2.3   | 
13.6  | 
 10 sonics   | 
 upwind   | 
2.8  | 
 5.1   | 
13.6  | 
 1x sonics, & etherant worth ~.3   | 
 downwind2   | 
2.9  | 
 8   | 
 13.6   | 
 12 sonics   | 
profile  | 
 2.5   | 
  | 
 12.6   | 
 3-trh, licor   | 
We put a 3rd supply to split the larger load.