Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Section
Column

M21

ht (m)

serial port

sensor

status

0.5

s1

CSAT

ok

0.5

s2

TRH

NG, fan running, high current (>1A), no data

 

s3

gps

ok

1

s5

CSAT

ok

1

s6

Licor

NG, blows fuses

1

s7

PTB220 p

ok

1.5

s8

TRH

NG, fan speed unsteady, no data

2

s9

CSAT

NG, blows fuses

2

s10

Licor

NG. No data

2

s11

TRH

NG, 1.2A, no data

3

s12

CSAT

ok

3

s13

TRH

NG, 1.3A

4

s14

CSAT

ok

4

s15

TRH

NG. 0.1 A but no data, no fan

5

s16

CSAT

NG 0.3 A, no data

5

"

kh2o/serializer

?

5

s17

Paroscientific p

NG. 0.05 A, no data, tried *0100P4/r/n init

 

s18

Picarro PC

NG

Column

M22

ht (m)

Serial Port

Sensor

Status

6

S1

TRH

NG 0.1 A, no fan, no data

6

S2

Handar

ok

 

S3

gps

ok

8

S5

TRH (replaced SHT) ok

bad data (-40C), replacement OK

8

S6

Handar

ok

10

S7

CSAT

ok

10

"

KH2O/serializer

NG. Raw data: 0xffff

15

S8

TRH (replaced SHT) ok

bad data (-40C), replacement OK

15

S9

Handar

ok

20

S10

CSAT

ok

20

S11

PTB 220 p

ok

...